Schneider
myCoreAI integrates with Schneider Electric EcoStruxure Building Operation (EBO) following the same pattern as other BMS integrations: myCoreAI reads sensor and meter values out of EBO and writes a limited, agreed set of setpoints back. This page covers what is specific to EBO.
Integration model
On the EBO side, a dedicated Myrspoven top-level folder holds three subfolders:
Read — every value myCoreAI reads from EBO (indoor temperatures, pressures, energy meters, equipment status, current setpoints).
Write — every setpoint myCoreAI writes back into EBO.
Overwrite Bindings — bindings that route written values to the actual EBO points, with a fallback template that takes over if writes stop.
Two connection paths are supported:
On-premise via the Myrspoven edge — a virtual server in the building network bridging EBO to the Myrspoven cloud.
Cloud-based via a Schneider SmartConnector. This path requires an additional failsafe (see Failsafe time).
EBO retains control of the building. myCoreAI only reaches the signals listed in Read, Write, and Overwrite Bindings.
Monitoring
Two surfaces provide a quick health check.
myPortal Blueprint view. Each sensor carries a color-coded status.
Black
Sensor disabled or broken
Red
One degree or more above the threshold
Orange
Above the threshold
Light blue
Below the minimum threshold
Blue
One degree or more below the minimum threshold
EBO ProcessViewer. The Myr_D and Myr_DS processes sit under the Myrspoven folder.
Myr_D — binary on/off indicator. Green means myCoreAI is running.
Myr_DS — indicates a successful write into EBO. Brief red states are normal and clear within 15 minutes. Persistent red: confirm the write process is enabled, then check the spov process for an active error.
The cloud icon above each sensor in EBO shows the setpoint chosen by myCoreAI. To pause optimization on a single circuit, open the cloud display's control panel and deactivate that circuit. The loop reverts to its original setpoint.
Sensor readings out of range
Check the bottleneck list. It surfaces sensors running too cold or too hot. Adjust the sensor's Min/Max, or disable a sensor in a bad location.
Account for the environment. Drafts, poor insulation, and direct sunlight produce misleading readings. Fix the physical cause before adjusting the model.
Choose the right scope. To shift the whole building warmer, raise Max on all sensors. To stop a single outlier from dominating, lower its Min.
Adaptive min/max is provisional. Under building settings, adaptive min/max limits how far myCoreAI may deviate from the original setpoint. Remove the restriction once the underlying issue is resolved.
RMSE and automatic fallback
Each building has an RMSE limit (default 1.7) tracking sensor deviation from expected behavior. When the limit is exceeded, myCoreAI deactivates automatically and the building reverts to EBO's original control logic.
To restore optimization:
Fix the underlying sensor issue. myCoreAI does not resume while large deviations remain.
Remove the Myr_DS lock by double-clicking it.
SmartConnector dropped its connection
Symptoms: read process turns red, signals start dropping, orange dot appears on Myr_DS and Myr_D. Recovery: restart the SmartConnector.
Verifying data accuracy in EBO
When commissioning or auditing a building, walk through the three Myrspoven folders and confirm the values.
Read folder (Myrspoven → Read)
For a Read signal, the left arrow (<-) in the Signalkey indicates the source of the value; the bidirectional arrow indicates the logging point used downstream.
Write folder (Myrspoven → Write)
Every value must match what appears in the EBO image. Mismatch: check the Signalkey.
For a Write signal, the left arrow shows the EBO write value read back; the right arrow shows the write value held on the Myrspoven side.
Overwrite Bindings folder (Myrspoven → Overwrite Bindings)
Values must match the corresponding Write folder values. Mismatch means the binding key is wrong.
Missing or faulty values mean the Signalkey needs checking.
For an Overwrite Binding, the left arrow points to the Myr_ut template (holding the fallback value); the right arrow points to the signal being written.
Failsafe time (cloud integrations)
SmartConnector-based integrations require a Failsafe Time parameter — a watchdog on the data flowing from myCoreAI into the cloud connector.
Duration: 900 seconds (15 minutes).
Behavior: if no updated value arrives within the window, the failsafe deactivates the cloud-side integration and reverts to default values. The building continues on EBO's own logic rather than stale setpoints.
The failsafe guarantees that an outage on the myCoreAI side cannot leave EBO running indefinitely on outdated values.
What partners provide
To onboard an EBO building:
The agreed signal list — read points and writable setpoints.
An EBO user with access to the Myrspoven folder structure (Read, Write, Overwrite Bindings).
Either a virtual server for the Myrspoven edge or a SmartConnector setup.
A point of contact at the Schneider integrator for commissioning.
For general troubleshooting not specific to EBO, see Troubleshooting.
Last updated
Was this helpful?

