Heating
Last updated
Was this helpful?
This page covers the source-specific heuristics and assumptions behind district heating in the Golden Report.
AHU — air handling unit
District heating is split into three buckets:
Tap water
Other
Heating
Heating is the remainder after tap water and Other.
Other covers district-heating use outside heating circuits and air handling units.
The remaining heating energy is split between:
Heating circuits
Air handling units
The default split is 60% heating circuits and 40% air handling units.
If you have a better building-specific split, Myrspoven uses that instead.
Tap-water use is estimated as the average of the two lowest district-heating months.
This usually captures warm months, when space-heating demand is low.
The estimate requires:
At least 8 months of energy data
Data for July and August
The estimate is capped at 5 kWh/m²/month.
If data is missing, tap water defaults to 1.6 kWh/m²/month.
The myCoreAI-controlled share is the heating used by:
Heating circuits
Air handling units in heating mode
That total is then weighted by uptime for the period.
Heating calculations are done separately for each component type.
Heating circuits use hourly averages, then aggregate across controlled circuits and time stamps.
Air handling units use hourly averages in heating mode, then aggregate across controlled units and time stamps.
Two inputs improve accuracy most:
Your real tap-water figure
Your real heating-circuit / AHU split
Share them with your Myrspoven representative to replace the defaults.
Last updated
Was this helpful?
Was this helpful?

