Cooling
Last updated
Was this helpful?
This page covers the source-specific heuristics and assumptions behind district cooling in the Golden Report.
AHU — air handling unit
District cooling is split into three buckets:
Cooling circuits
Air handling units in cooling mode
Other
Other covers cooling uses outside those HVAC components.
A monthly Other amount is set aside first — either a figure you provide or the estimate described below.
The remaining cooling energy is split between:
Cooling circuits
Air handling units
The default split is 50% / 50%.
If you have a better building-specific split, Myrspoven uses that instead.
If you do not provide an Other figure, it is estimated as the average of the two lowest district-cooling months.
This assumes those months mostly reflect non-HVAC cooling use.
The estimate requires at least 8 months of energy data.
If less data is available, Other defaults to 0.
The myCoreAI-controlled share is the cooling used by:
Cooling circuits
Air handling units in cooling mode
That total is then weighted by uptime for the period.
Cooling calculations are done separately for each component type.
Cooling circuits use hourly averages, then aggregate across relevant components and time stamps.
Air handling units use hourly averages during cooling mode, then aggregate across relevant units and time stamps.
Two inputs improve accuracy most:
Your real Other cooling figure
Your real cooling-circuit / AHU split
Share them with your Myrspoven representative to replace the defaults.
Last updated
Was this helpful?
Was this helpful?

