Draught control
Last updated
Was this helpful?
Draught control is a myCoreAI feature that prevents perimeter discomfort from cold air falling along windows and façades — kallras in Swedish — during cold-weather office hours. myCoreAI raises the lower bound on heating-circuit supply temperatures so radiator water stays warm enough to offset the downdraught, even when room temperature is already on target.
myCoreAI activates draught control when both conditions hold:
Time of day: 07:00–17:00 (building local time)
Outdoor temperature: below 5 °C
Outside these conditions, the bounds produced by other pipeline steps are left unchanged.
myCoreAI raises the lower bound of every heating-circuit supply-temperature setpoint by 15% of that signal's configured min–max range.
15–70 °C (typical)
~8 °C
The upper bound is untouched. myCoreAI can still push the setpoint higher when heat demand warrants it — only the floor moves up.
Draught control is one step in the sequence of bound adjustments myCoreAI applies before each optimization run. It only tightens the lower bound upward; it never widens it. If an earlier step has already pushed the lower bound above the draught-corrected level, draught control has no further effect at that timestep.
Draught control acts on heating-circuit supply temperatures only. myCoreAI does not modify the following signals through this feature:
Air-handling-unit supply-air setpoints
Zone-asset schedules
Indoor temperature targets configured per climate group
Last updated
Was this helpful?
Was this helpful?

