Draught control
Draught control is a myCoreAI feature that prevents perimeter discomfort from cold air falling along windows and façades — kallras in Swedish — during cold-weather office hours. myCoreAI raises the lower bound on heating-circuit supply temperatures so radiator water stays warm enough to offset the downdraught, even when room temperature is already on target.
Trigger conditions
myCoreAI activates draught control when both conditions hold:
Time of day: 07:00–17:00 (building local time)
Outdoor temperature: below 5 °C
Outside these conditions, the bounds produced by other pipeline steps are left unchanged.
Effect
myCoreAI raises the lower bound of every heating-circuit supply-temperature setpoint by 15% of that signal's configured min–max range.
15–70 °C (typical)
~8 °C
The upper bound is untouched. myCoreAI can still push the setpoint higher when heat demand warrants it — only the floor moves up.
Position in the bounds pipeline
Draught control is one step in the sequence of bound adjustments myCoreAI applies before each optimization run. It only tightens the lower bound upward; it never widens it. If an earlier step has already pushed the lower bound above the draught-corrected level, draught control has no further effect at that timestep.
Scope
Draught control acts on heating-circuit supply temperatures only. myCoreAI does not modify the following signals through this feature:
Air-handling-unit supply-air setpoints
Zone-asset schedules
Indoor temperature targets configured per climate group
Last updated
Was this helpful?

